Vermogenstabel voor
krachtstroomkabel bij 400V
|
P
|
I
|
Kabellengte
|
|
[kW]
|
[A]
|
[m]
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
25
|
50
|
75
|
100
|
150
|
250
|
350
|
500
|
600
|
700
|
900
|
1000
|
|
4,6
|
10
|
1,5
|
1,5
|
1,5
|
1,5
|
1,5
|
2,5
|
4
|
6
|
6
|
10
|
10
|
10
|
|
9,2
|
20
|
1,5
|
1,5
|
2,5
|
2,5
|
4
|
6
|
10
|
16
|
16
|
16
|
25
|
25
|
|
14
|
30
|
4
|
4
|
4
|
4
|
6
|
10
|
16
|
16
|
25
|
25
|
35
|
35
|
|
18
|
40
|
6
|
6
|
6
|
6
|
6
|
10
|
16
|
25
|
35
|
35
|
50
|
50
|
|
23
|
50
|
10
|
10
|
10
|
10
|
10
|
16
|
25
|
35
|
35
|
50
|
50
|
70
|
|
28
|
60
|
10
|
10
|
10
|
10
|
10
|
16
|
25
|
35
|
50
|
50
|
70
|
70
|
|
32
|
70
|
16
|
16
|
16
|
16
|
16
|
25
|
35
|
50
|
50
|
70
|
70
|
95
|
|
37
|
80
|
16
|
16
|
16
|
16
|
16
|
25
|
35
|
50
|
70
|
70
|
95
|
95
|
|
41
|
90
|
25
|
25
|
25
|
25
|
25
|
25
|
35
|
50
|
70
|
70
|
95
|
120
|
|
46
|
100
|
25
|
25
|
25
|
25
|
25
|
35
|
50
|
70
|
70
|
95
|
120
|
120
|
|
57
|
125
|
35
|
35
|
35
|
35
|
35
|
35
|
50
|
70
|
95
|
120
|
150
|
150
|
|
69
|
150
|
50
|
50
|
50
|
50
|
50
|
50
|
70
|
95
|
120
|
120
|
150
|
185
|
|
80
|
175
|
70
|
70
|
70
|
70
|
70
|
70
|
70
|
120
|
120
|
150
|
185
|
240
|
|
92
|
200
|
70
|
70
|
70
|
70
|
70
|
70
|
95
|
120
|
150
|
185
|
240
|
240
|
|
115
|
250
|
95
|
95
|
95
|
95
|
95
|
95
|
120
|
150
|
185
|
240
|
240
|
300
|
|
138
|
300
|
120
|
120
|
120
|
120
|
120
|
120
|
120
|
185
|
240
|
240
|
300
|
300
|
|
161
|
350
|
150
|
150
|
150
|
150
|
150
|
150
|
150
|
240
|
240
|
300
|
400
|
400
|
|
184
|
400
|
240
|
240
|
240
|
240
|
240
|
240
|
240
|
240
|
300
|
300
|
400
|
500
|
|
|
|
|
Oppervlakte is gegeven
in mm²
|
|
|
|
|
|
|
Spanningverlies 5%
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Deze tabel is een richtlijn,
er kunnen derhalve geen rechten aan ontleend worden.
|